The BH to BL range of Klargester BioDisc® treatment plants are high performance package units for residential, business and Leisure applications.
These units utilise proven rotating biological contactor (RBC) technology which Klargester has been using now for over 30 years.
Process Features
- Klargester Patented Flow Management (KPFM)
- No Process maintenance required
- Simple Mechanics
- Self Generating bacteriological process
- KPFM provides capability to adjust plant performance
- Compliance with BS 6297 and Building Regulations Part H2
- Low head loss
- Sludge pump return in final settlement tank to enhance performance
- No odour, fly or environmental nuisance
- Silent in operation
- Manufactured under the quality procedures of BS ISO9001: 2000
- Owls Hall offer a full commissioning and after sales service involving planned maintenance visits.
Please visit our servicing section for more information.
For temporary storage solutions click here.
Klargester Patented Flow Management (KPFM)
The volume of waste water from residential, business and leisure properties is highly variable. The use of a patented flow management device means that the flow and biological loads are consistent thus providing a constant high quality of discharge and preventing waste water bypassing the system.
Saftey Features
- Low profile lockable covers
- Fully removable covers for easy maintenance.
- Full platform access to motor and bearings
- Secure lockable control panel
- Integrated loss of rotation alarm
Low Operating Cost
- Runs from either single or 3 phase
- Require only 250 or 270 watt motors
Control Panel
- Inversion device included within the panel
- Single phase power supply to the panel converted to three phase prior to connection to the motor
Direct Drive
- No requirement for chain or belt
- Reduces and simplifies maintenance
Two-Part Shaft
- Reduces bearing wear
- Provides performance upgrade options
Separate sample chambers are available for accurate and convenient effluent sampling, as required by the relevant authorities
All treatment plants should preferably be no closer than 7m from the nearest habitable property to comply with local building authority regulations.
Owls Hall offer a full Installation service. Please visit our Installation section for more information.
Klargester Biodisc BH – BL Specification Table
Unit Size | BH | BJ | BK | BL |
---|---|---|---|---|
Maximum Daily BOD (kg) | 4.5 | 6.0 | 7.5 | 9.0 |
Maximum Daily Flow (m³) | 15 | 20 | 25 | 30 |
BioDisc® | ||||
Length (mm) | 7755 | 7755 | 7755 | 7755 |
Width (mm) | 2455 | 2455 | 2455 | 2455 |
Inlet Invert depth (mm) | 600 | 600 | 600 | 600 |
Depth below inlet (mm) | 1790 | 1790 | 1790 | 1790 |
Outlet Invert Depth (mm) | 750 | 750 | 750 | 750 |
Overall Height (mm) | 2830 | 2830 | 2830 | 2830 |
Height to rim of cover (mm) | 2500 | 2500 | 2500 | 2500 |
Empty Weight (kg) | 3000 | 3100 | 3200 | 3300 |
Standard Power Supply | 3 phase | 3 phase | 3 phase | 3 phase |
Optional Power Supply | 1 phase | 1 phase | 1 phase | 1 phase |
Motor Rating – 1phase/3phase (watts) | 250 | 250 | 370 | 370 |
Full load current 1 phase (amps) | 1.95 | 1.95 | 2.35 | 2.35 |
Full load current 3 phase (amps) | 0.88 | 0.88 | 1.35 | 1.35 |
Sludge Return Pump Rating (watts) | 250 | 250 | 250 | 250 |
This Chart is a general guide
Owls Hall are able to assist with the legal requirement of obtaining a consent to discharge from the Environment Agency or other regulatory body prior to installation.
All our treatment plants and and septic tanks are installed in line with the British Water Flows and Loads v4
*Based on the number of people in full time residential occupation
All Klargester products have a full initial 12 month warranty covering all mechanical and electrical components against malfunction, provided the unit has not been subject to damage or abuse.
Download Area
- BioDisc BE – BL Brochure
- BioDisc Installation guidelines for single piece units BH, BJ & NJ PD0170-09
- BioDisc Installation guidelines for units BJ, BK, BL, NJ, NK & NL PD0173-08
- BioDisc Installation & operation guidlines for single piece units BH – BL & NH – NL PD0351-02
- BioDisc Installation instructions for N3 to N5 Nitrification PD0064-01
- Sample Chamber Diagram 800776-07
- Sample Chambers Installation guidelines PD0071-03